- SECTION 08565
-
- VINYL (PVC) WINDOWS
- NOTE ** ALSIDE Window Systems vinyl windows, patio doors,
- and specialty windows.
- NOTE **
- NOTE ** This section is based on products manufactured by:
- NOTE ** ALSIDE Window Systems
- NOTE ** P.O. Box 2010 Akron OH 44309
- NOTE ** Tel: (800) 257-4335
- NOTE ** Fax: (330) 922-5387
- NOTE **
- NOTE ** ALSIDE Window Systems offer a full selection of
- vinyl windows, patio doors, and specialty windows.
- NOTE **
- NOTE ** SECTION 08565 - VINYL (PVC) WINDOWS, Copyright
- 1998, The Architect's Catalog, Inc.
-
- PART 1 GENERAL
-
- 1.1 SECTION INCLUDES
-
- A. Single Hung Window Units.
-
- B. Double Hung Window Units.
-
- C. Horizontal Sliding Window Units.
-
- D. Horizontal Sliding Patio Door Units.
-
- E. Casement Window Units.
-
- 1.2 RELATED SECTIONS
- NOTE ** Delete any sections below not relevant to this
- project; add others as required.
-
- A. Section 05400 - Cold Formed Metal Framing.
-
- B. Section 06100 - Rough Carpentry.
-
- C. Section 07900 - Joint Sealers.
-
- D. Section 09100 - Metal Support Systems.
-
- 1.3 REFERENCES
- NOTE ** Delete any references below not relevant to this
- project; add others as required.
-
- A. AAMA 101 - Voluntary Standard for Aluminum and Poly
- (Vinyl Chloride) (PVC) Prime Windows and Glass Doors.
-
- B. NFRC 100 - Thermal Properties; National Fenestration
- Rating Council.
-
- C. ASTM D 3656 - Standard Specification for Insect Screening
- and Louver Cloth Woven from Vinyl-Coated Glass Fiber
- Yarn.
-
- D. ASTM D 3678 - Standard Specification for Rigid Poly
- (Vinyl Chloride) (PVC) Interior Profile Extrusions.
-
- E. ASTM D 4028 - Standard Specification for Solar Screening
- Woven from Vinyl-Coated Fiber Glass Yarn.
-
- F. ASTM D 4099 - Standard Specification for Poly (Vinyl
- Chloride) (PVC) Prime Windows/Sliding Glass Doors.
-
- G. ASTM E 774 - Standard Specification for Sealed Insulating
- Glass.
-
- H. IGCC - Classification of Insulating Glass Units;
- Insulated Glass Certification Council.
-
- 1.4 SUBMITTALS
-
- A. Submit under provisions of Section 01300.
-
- B. Product Data: Manufacturer's standard details and
- catalog data demonstrating compliance with referenced
- standards; include manufacturer's standard installation
- instructions.
-
- C. Drawings: Manufacturer's product drawings showing
- details of fabrication, hardware, weatherstripping,
- fasteners, screens, glazing, accessories, and related
- items.
-
- D. Verification Samples: Operating sample of each window
- type specified illustrating fabrication, hardware,
- glazing, screen, and finish.
-
- E. Test Reports: For each window type specified, furnish
- test reports from accredited independent testing
- laboratory certifying that identical or larger window
- units meet requirements specified for air infiltration,
- water penetration and structural performance by ASTM D
- 4099 or AAMA 101, for thermal performance by NFRC, and
- for seal integrity of insulating glass units by IGCC.
-
- F. Closeout Submittals: Warranty documents, properly
- executed.
-
- 1.5 QUALITY ASSURANCE
-
- A. Manufacturer Qualifications: Minimum ten (10) years
- experience producing vinyl (PVC) windows.
-
- 1.6 DELIVERY, STORAGE AND HANDLING
-
- A. Deliver windows to project site in undamaged condition;
- handle windows to prevent damage to components and to
- finishes.
-
- B. Store windows out of contact with ground; protect windows
- from weather and construction traffic in well-ventilated
- area.
-
- 1.7 WARRANTY
-
- A. Furnish manufacturer's standard warranty against
- deficiencies in materials or fabrication.
-
-
- PART 2 PRODUCTS
-
- 2.1 MANUFACTURERS
-
- A. Acceptable Manufacturer: ALSIDE Window Systems;, P.O.
- Box 2010 Akron, OH 44309; ASD. Tel: (800) 257-4335, Fax:
- (330) 922-5387.
-
- B. Substitutions: Not permitted.
- NOTE ** Delete the following Article if no single-hung
- window units required.
-
- 2.2 SINGLE HUNG WINDOW UNITS
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0500 single-hung window units.
-
- A. Acceptable Product: ALSIDE MODEL 0500.
- 1. Grade: ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
- 48-inch wide by 72-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.15 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.33.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, overlapping butt-joint
- construction, joined with screws into integral screw
- ports; sloped sill for positive drainage.
- 8. Sash: PVC extrusions, tilt-in operation of lower
- sash for cleaning, with spiral balances, integral
- double walled lift rail for added strength,
- interlocking with fixed meeting rail of main frame,
- and cam-type sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0100 single-hung new construction window units in
- Grade 20.
-
- B. Acceptable Product: ALSIDE MODEL 0100.
- 1. Grade: ASTM D 4099 Grade 20, AAMA 101 Grade R20, for
- 48-inch wide by 72-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 3.0 pounds per square foot.
- b. Air infiltration: 0.10 cubic feet per minute per
- linear foot at 25 miles per hour.
- c. Test pressure sustained without damage: 30
- pounds per square foot.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.31.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 3/4 inch unit
- thickness, with SSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 3/4
- inch unit thickness, with SSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners.
- 8. Sash: Narrow-line fusion-welded PVC extrusions,
- mitered corners, tilt-in operation of lower sash for
- cleaning, with spiral balances, integral lift rail
- for added strength, interlocking with fixed meeting
- rail of main frame, and cam-type sweep locks and
- keepers.
- 9. Nailing fin: Extruded PVC, 1-1/8 inches wide, four
- sides.
- 10. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 11. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Delete the following Article if no double-hung
- window units required.
-
- 2.3 DOUBLE HUNG WINDOW UNITS
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0901 double-hung window units.
-
- A. Acceptable Product: ALSIDE MODEL 0901.
- 1. Grade: ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
- 48-inch wide by 72-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 5.0 pounds per square foot.
- b. Air infiltration: 0.16 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.34.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, telescoping butt-joint
- construction reinforced at corners, joined with
- screws into integral screw ports; sloped sill for
- positive drainage.
- 8. Sash: PVC extrusions, aluminum reinforced horizontal
- members for window units over 28-7/8 inches wide,
- tilt-in operation of upper and lower sash for
- cleaning, with field-adjustable spiral balances,
- integral double walled lift rail for added strength,
- interlocking meeting rails and cam-type sweep locks
- and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0601 double-hung window units in standard Grade 45.
-
- B. Acceptable Product: ALSIDE MODEL 0601.
- 1. Grade: ASTM D 4099 Grade 45, AAMA 101 Grade R45, for
- 47-inch wide by 60-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 6.0 pounds per square foot.
- b. Air infiltration: 0.13 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.47.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.32.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; concealed screen track.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, tilt-in operation of
- upper and lower sash for cleaning, with field-
- adjustable spiral balances, double lift rail on
- bottom sash, interlocking meeting rails, and cam-type
- sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 3001 double-hung window units.
-
- C. Acceptable Product: ALSIDE MODEL 3001.
- 1. Grade: ASTM D 4099 Grade 45, AAMA 101 Grade R45, for
- 48-inch wide by 72-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.19 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.34.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 15/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 15/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, butt-joint construction,
- sloped hospital sill for positive drainage.
- 8. Sash: PVC extrusions, mitered corners joined with 4
- screws per corner into heavy duty corner gussets;
- tilt-in operation of upper and lower sash for
- cleaning, with field-adjustable spiral balances;
- integral double walled lift rail for added strength,
- interlocking meeting rails on top and bottom sash,
- and cam-type sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete options specified in the following two
- paragraphs if not required.
- 10. Reinforcement: Steel reinforced frame and/or sash.
- 11. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- O201 double-hung window units.
-
- D. Acceptable Product: ALSIDE MODEL O201.
- 1. Grade: ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
- 48-inch wide by 60-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.15 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.51.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.36.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; sloped sill for positive drainage.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, tilt-in operation of
- upper and lower sash for cleaning, with field-
- adjustable spiral balances, interlocking meeting
- rails, and cam-type sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0401 double-hung window units.
-
- E. Acceptable Product: ALSIDE MODEL 0401.
- 1. Grade: ASTM D 4099 Grade 35, AAMA 101 Grade R35, for
- 36-inch wide by 60-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.50 pounds per square
- foot.
- b. Air infiltration: 0.15 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.33.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, telescoping butt-joint
- construction reinforced at corners, joined with
- screws into integral screw ports; sloped sill for
- positive drainage.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, tilt-in operation of
- upper and lower sash for cleaning, with field-
- adjustable spiral balances, double lift rail on
- bottom sash, interlocking meeting rails, and cam-type
- sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
-
- F. Acceptable Product: ALSIDE MODEL 0301.
- 1. Grade: ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
- 48-inch wide by 60-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.15 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.51.
- 3. Thermal performance, in accordance with NFRC 100, for
- 48-inch wide by 72-inch high window unit: U-Value
- 0.36.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 3/4 inch unit
- thickness, with SSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 3/4
- inch unit thickness, with SSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; sloped sill for positive drainage,
- integral J-channel.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, tilt-in operation of
- upper and lower sash for cleaning, with field-
- adjustable spiral balances, interlocking meeting
- rails, and cam-type sweep locks and keepers.
- 9. Nailing fin: Extruded PVC, four sides, 1.75 wide.
- 10. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 11. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Delete the following Article if no horizontal-
- sliding window units required.
-
- 2.4 HORIZONTAL SLIDING WINDOW UNITS
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0902 horizontal-sliding window units.
-
- A. Acceptable Product: ALSIDE MODEL 0902.
- 1. Grade: ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
- 72-inch wide by 48-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.20 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.34.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, butt-joint construction at
- corners, joined with screws into integral screw
- ports; multi-chambered weep system with wind-blocking
- covers.
- 8. Sash: PVC extrusions, aluminum-reinforced vertical
- members for window units over 29-1/2 inches high,
- lift-out operation of both operable sash units, with
- nylon-encased metal dual-roller system, full-
- interlocking meeting rails, full sash capture at
- jamb, sash vent lock, theft-deterrent blocks, and cam-
- type sweep locks and keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0602 horizontal-sliding window units.
-
- B. Acceptable Product: ALSIDE MODEL 0602.
- 1. Grade: ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
- 72-inch wide by 51-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 6.5 pounds per square foot.
- b. Air infiltration: 0.20 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.47.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.31.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; step sill for positive drainage,
- concealed screen track.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, lift-out operation of
- both operable sash units, with nylon-encased metal
- dual-roller system, full-interlocking meeting rails,
- full sash capture at jamb, sash vent lock, theft-
- deterrent blocks, cam-type locks with keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 3002 horizontal-sliding window units.
-
- C. Acceptable Product: ALSIDE MODEL 3002.
- 1. Grade: ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
- 72-inch wide by 50-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 5.0 pounds per square foot.
- b. Air infiltration: 0.16 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.35.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 15/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 15/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners.
- 8. Sash: PVC extrusions, mitered corners with heavy
- duty corner gussets secured by four (4) screw
- fasteners each corner, lift-out operation of both
- operable sash units, with nylon-encased metal dual-
- roller system, full-interlocking meeting rails, full
- sash capture at jamb, sash vent lock, theft-deterrent
- blocks, dual chrome-plated cam-type locks with
- stainless steel keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0102 horizontal-sliding window units.
-
- D. Acceptable Product: ALSIDE MODEL 0102.
- 1. Grade: ASTM D 4099 Grade 25, AAMA 101 Grade R25, for
- 72-inch wide by 48-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 5.25 pounds per square
- foot.
- b. Air infiltration: 0.10 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.31.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 3/4 inch unit
- thickness, with SSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 3/4
- inch unit thickness, with SSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; weeps in sill for positive drainage,
- extruded PVC nailing fin four (4) sides.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, lift-out operation of
- operable sash unit, with full-interlocking meeting
- rail, full sash capture at jamb, cam-type locks with
- keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- O202 horizontal-sliding window units.
-
- E. Acceptable Product: ALSIDE MODEL O202.
- 1. Grade: ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
- 60-inch wide by 36-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 6.0 pounds per square foot.
- b. Air infiltration: 0.12 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.35.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; weeps in sill for positive drainage.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, lift-out operation of both operable
- sash units, with nylon-encased metal dual-roller
- system, full-interlocking meeting rails, full sash
- capture at sill, cam-type locks with keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- O402 horizontal-sliding window units.
-
- F. Acceptable Product: ALSIDE MODEL O402.
- 1. Grade: ASTM D 4099 Grade 40, AAMA 101 Grade R40, for
- 72-inch wide by 48-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 5.25 pounds per square
- foot.
- b. Air infiltration: 0.20 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 48-inch high window unit: U-Value
- 0.33.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, butt-joint construction at
- corners, joined with screws into integral screw
- ports; multi-chambered weep system with wind-blocking
- covers.
- 8. Sash: PVC extrusions, fusion-welded narrow-line
- construction, mitered corners, lift-out operation of
- both operable sash units, with nylon-encased metal
- dual-roller system, full-interlocking meeting rails,
- full sash capture at jamb, cam-type locks with
- keepers.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- NOTE ** Delete the following Article if no horizontal-
- sliding patio door units required.
-
- 2.5 HORIZONTAL SLIDING PATIO DOOR UNITS
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 6100 horizontal-sliding patio door units.
-
- A. Acceptable Product: ALSIDE MODEL 6100.
- 1. Grade: ASTM D 4099 Grade 35, AAMA 101 Grade R35, for
- 69-inch wide by 79-inch high door unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 4.5 pounds per square foot.
- b. Air infiltration: 0.15 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional colonial grooved or tinted glazing is
- specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.54.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.39.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Colonial grooved glazing and
- tinted glazing are options; consult with
- manufacturer.
- 4. Glazing: Sealed insulating glass unit, 7/8 inch unit
- thickness, with fully-tempered DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 7/8
- inch unit thickness, with fully-tempered DSB glass
- and argon gas fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: Vinyl-clad wood, triple-screw butt-joint
- construction; sloped vinyl sill with steel roller
- track.
- 8. Sash: PVC extrusions, butt-joint construction, steel-
- reinforced vertical members, operable sash unit with
- adjustable dual-roller system, full-interlocking
- meeting rails, full sash capture at jamb, and
- latching hardware with keeper.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement; four-point adjustable rollers.
- NOTE ** Delete the options in the following four paragraphs
- if not required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- 11. Hardware operation: Keyed lock on exterior side,
- with two (2) keys.
- 12. Hardware finish: Brass.
- 13. Vent lock.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 2100 horizontal-sliding patio door units.
- B. Acceptable Product: ALSIDE MODEL 2100.
- 1. Grade: ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
- 72-inch wide by 80-inch high door unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 3.75 pounds per square
- foot.
- b. Air infiltration: 0.09 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional colonial grooved or tinted glazing is
- specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.50.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.34.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Colonial grooved glazing and
- tinted glazing are options; consult with
- manufacturer.
- 4. Glazing: Sealed insulating glass unit, 7/8 inch unit
- thickness, with fully-tempered DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 7/8
- inch unit thickness, with fully-tempered DSB glass
- and argon gas fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, mechanical butt-joint
- construction, stainless steel track; sloped vinyl
- sill for positive drainage.
- 8. Sash: PVC extrusions, fusion-welded construction,
- mitered corners, steel-reinforced vertical members on
- operable panel, operable sash unit with adjustable
- dual-roller system, full-interlocking meeting rails,
- full sash capture at jamb, and latching hardware with
- keeper.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement; four-point adjustable rollers.
- NOTE ** Delete options specified in the following two sub-
- paragraphs if not required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- 11. Hardware operation: Keyed lock on exterior side,
- with two (2) keys.
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 1100 horizontal-sliding patio door units.
-
- C. Acceptable Product: ALSIDE MODEL 1100.
- 1. Grade: ASTM D 4099 Grade 30, AAMA 101 Grade R30, for
- 72-inch wide by 80-inch high door unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 3.75 pounds per square
- foot.
- b. Air infiltration: 0.09 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional colonial grooved or tinted glazing is
- specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.49.
- 3. Thermal performance, in accordance with NFRC 100, for
- 72-inch wide by 96-inch high door unit: U-Value
- 0.34.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Colonial grooved glazing and
- tinted glazing are options; consult with
- manufacturer.
- 4. Glazing: Sealed insulating glass unit, 7/8 inch unit
- thickness, with fully-tempered DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 7/8
- inch unit thickness, with fully-tempered DSB glass
- and argon gas fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners; vinyl sill with aluminum roller
- track.
- 8. Sash: PVC extrusions, fusion-welded construction,
- mitered corners, steel-reinforced vertical members on
- operable sash unit with adjustable dual-roller
- system, full-interlocking meeting rails, full sash
- capture at jamb, and latching hardware with keeper.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement; four-point adjustable rollers.
- NOTE ** Delete options specified in the following two sub-
- paragraphs if not required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
- 11. Hardware operation: Keyed lock on exterior side,
- with two (2) keys.
- NOTE ** Delete the following Article if no casement window
- units required.
-
- 2.6 CASEMENT WINDOW UNITS
- NOTE ** Retain the following paragraph if specifying ALSIDE
- 0961 casement window units.
-
- A. Acceptable Product: ALSIDE MODEL 0961.
- 1. Grade: ASTM D 4099 Grade 50, AAMA 101 Grade R50, for
- 26-inch wide by 50-inch high window unit; exceeding
- grade requirements as follows:
- a. Water test pressure: 5.25 pounds per square
- foot.
- b. Air infiltration: 0.04 cubic feet per minute per
- linear foot at 25 miles per hour.
- NOTE ** Delete one of the following two sub-paragraphs;
- first is for standard glazing, second is for low-e
- glazing with argon gas fill. Consult with
- manufacturer for thermal performance data if
- optional obscure or tinted glazing is specified.
- 2. Thermal performance, in accordance with NFRC 100, for
- 30-inch wide by 60-inch high window unit: U-Value
- 0.44.
- 3. Thermal performance, in accordance with NFRC 100, for
- 30-inch wide by 60-inch high window unit: U-Value
- 0.30.
- NOTE ** Delete one of the following two sub-paragraphs to
- specify glazing type required; first is for
- standard glazing, second is for low-e glazing with
- argon gas fill. Obscure glazing and tinted glazing
- are options; consult with manufacturer.
- 4. Glazing: Sealed insulating glass unit, 13/16 inch
- unit thickness, with DSB glass.
- 5. Glazing: Low-e sealed insulating glass unit, 13/16
- inch unit thickness, with DSB glass and argon gas
- fill.
- 6. Sealed Insulating Glass Units: Conform to ASTM E
- 774, Level CBA, utilizing PPG Warm-Edge "Intercept"
- Spacer System.
- 7. Frame: PVC extrusions, fusion-welded construction,
- mitered corners.
- 8. Sash: PVC extrusions, fusion-welded construction,
- mitered corners, operable sash unit with single-
- handle multi-point locking system, positive-action
- rotary-crank operator system, with handle.
- 9. Insect screening: Roll-formed or extruded aluminum
- channel frames, with 18 by 16 fiberglass mesh secured
- with continuous vinyl gasket, removable for screen
- replacement.
- NOTE ** Delete the following paragraph if muntins are not
- required.
- 10. Muntins: Colonial grid installed between outer and
- inner glass panes during fabrication of insulating
- glass units.
-
- 2.7 FABRICATION
-
- A. Window/Door Units: Assemble units completely in factory,
- including operating hardware and glazing.
-
-
- PART 3 EXECUTION
-
- 3.1 EXAMINATION
-
- A. Verification of Conditions: Openings are in correct
- location, and of correct size, in accordance with
- approved shop drawings and manufacturer's installation
- instructions.
-
- B. Installer's Examination:
- 1. Have installer of this section examine conditions
- under which construction activities of this section
- are to be performed, then submit written notification
- if such conditions are unacceptable.
- 2. Transmit two copies of installer's report to
- Architect within 24 hours of receipt.
- 3. Beginning construction activities of this section
- before unacceptable conditions have been corrected is
- prohibited.
- 4. Beginning construction activities of this section
- indicates installer's acceptance of conditions.
-
- 3.2 INSTALLATION
-
- A. Install products specified in this section square, plumb
- and level, in accordance with approved shop drawings and
- manufacturer's installation instructions.
-
- B. Installation of joint sealers is specified in Section
- 07900.
-
- 3.3 ADJUSTING
-
- A. Adjust operating hardware for correct operation in
- accordance with manufacturer's installation instructions.
-
- 3.4 CLEANING
-
- A. Clean interior and exterior surfaces free of labels,
- mortar, plaster, paint, joint sealers, and other foreign
- matter to prevent damage to weatherstrip, and to prevent
- interference with operation of hardware.
-
- 3.5 PROTECTION
-
- A. Protect ventilators and operating parts from dirt and
- damage caused by subsequent construction activities.
-
- B. Replace units damaged by subsequent construction
- activities.
-
-
- END OF SECTION
-